          Model

          GP-M001

          GP-M010

          GP-M025

          GP-M100

          GP-M250

          GP-M400

          Rated pressure

          -14.50 to +14.50 PSI
          (-100 to +100 kPa)

          -14.5 to +145.0 PSI
          (-0.1 to +1 MPa)

          -14.5 to +362.6 PSI
          (-0.1 to +2.5 MPa)

          0 to +1450 PSI
          (0 to +10 MPa)

          0 to +3626 PSI
          (0 to +25 MPa)

          0 to+5802 PSI
          (0 to+40 MPa)

          Possible display range

          -17.40 to +17.40 PSI
          (-120.0 to +120.0 kPa)

          -30.5 to +161.0 PSI
          (-0.210 to +1.110 MPa)

          -52.2 to +400.3 PSI
          (-0.360 to +2.760 MPa)

          -145 to +1595 PSI
          (-1.00 to +11.00 MPa)

          -363 to +3989 PSI
          (-2.50 to +27.50 MPa)

          -580 to+6382 PSI
          (-4.00 to+44.00 MPa)

          Zero-cut pressure value

          ±0.5% of F.S.

          Burst pressure

          217.5 PSI (1500 kPa)

          2175 PSI (15 MPa)

          5075 PSI (35 MPa)

          14504 PSI (100 MPa)

          Display resolution

          kPa

          0.1

          1

          None

          MPa

          None

          0.001

          0.01

          PSI

          0.01

          0.1

          1

          bar

          0.001

          0.01

          0.1

          kgf/cm2

          Fluid type

          Gas or liquid that will not corrode the liquid contact part

          Liquid that will not corrode the liquid contact part

          Type of pressure

          Gage pressure

          Precision

          ±1.0% of F.S. or less*1

          Repeatability

          ±0.3% of F.S. or less*2

          Temperature characteristics

          ±0.6% of F.S./10°C 50°F

          Connection port

          G3/4 (Changes to the R male 1/8, R male 1/4, R male 3/8, G female 1/4, NPT male 1/8, and NPT male 1/4 option adapters are available.)

          Box rotation angle

          Maximum 330°

          Medium temperature

          -20 to +100°C -4°F to +212°F (no freezing/condensation)*3

          Power voltage

          10-30 VDC, Ripple (P-P): 10% max, Class 2 or LPS

          Current consumption

          50 mA or less (when 24 V: 32 mA or less, when 12 V: 48 mA or less. Not including load)*4

          Display method

          4 column, digital LED, red/Vertical inversion display possible

          Operation display light

          Operation indicator (output 1) (orange), Operation indicator (output 2) (orange)

          Hysteresis

          During hysteresis mode: variable (Difference between switch-on point and switch-off point is hysteresis)
          During window mode: fixed (0.5% of F.S.)

          Response

          Control output

          Selectable from 3 to 5000 ms

          Analog output

          As above + 2 ms (90% response)

          Output

          Output 1 control output

          NPN/PNP open collector (Selectable), Max. 250 mA (30 V max)
          Main unit residual voltage 1 V max, N.O./N.C. selectable

          Output 2
          replacement type

          Control output

          Analog output

          4-20 mA, maximum load resistance 500 Ω (When the electric voltage is more than 20 V)*5

          Environmental resistance

          Enclosure rating

          IP67

          Pressure resistance

          400 kPa (4 bar)

          4 MPa (40 bar)

          10 MPa (100 bar)

          30 MPa (300 bar)

          50 MPa (500 bar)

          Ambient temperature

          -20 to +80 °C -4 to 176 °F (No freezing and no condensation)

          Relative humidity

          35 to 85 % RH (No condensation)

          Vibration resistance

          IEC60068-2-6 20 G (10 to 2000 Hz, 2 hours each in the X, Y, and Z axis)

          Shock resistance

          IEC60068-2-27 50G (11 ms, 3 times for each of X, Y and Z direction)

          Material
          properties

          Wetted part

          Pressure port: SUSXM7, Diaphragm pressure port: Al2O3 (Alumina), O ring: FKM

          Other parts

          Housing metal portion: SUS304, SUS303, Housing plastic portion: PPSU, Air hole: PTFE, nickel-plated brass.

          Housing metal portion: SUS304, SUS303, Housing plastic portion: PPSU

          Applicable cable

          M12 connector 4 pin

          Weight

          Approx. 150 g

          *1 This is the value when considering linearity + hysteresis + repeatability in a stable environment of 23°C 73°F.
          *2 The repeatability, based on consistent conditions, is the variation in the value that will be displayed.
          *3 When the temperature of the piping exceeds 80°C 176°F, do not connect the cable.
          *4 Consumption current including output is 0.6 A and under.
          *5 The maximum load resistance R will be the values below in response to the electric voltage E. When 10-23V: R = {38 x (E-10) + 128} Ω When 23-30V: R = 622 Ω