Compact Switching Power Supply
MS2 series
Specs Compact Switching Power Supply MS2 series
| 
         Model  | 
        
         MS2-H50  | 
        
         MS2-H75  | 
        
         MS2-H100  | 
        
         MS2-H150  | 
        
         MS2-H300  | 
    |||
| 
         Image  | 
        
         
  | 
        
         
  | 
        
         
  | 
        
         
  | 
        
         
  | 
    |||
| 
         Input conditions  | 
        
         Input voltage  | 
        
         85 to 264 VAC, 110 to 370 VDC*1  | 
    ||||||
| 
         Frequency  | 
        
         47 to 63 Hz, DC*1  | 
    |||||||
| 
         Inputconditions  | 
        
         Input current (100/200 VAC)  | 
        
         1.3/0.7A or less  | 
        
         1.9/0.9A or less  | 
        
         2.1/1.3A or less  | 
        
         2.2/1.1A or less  | 
        
         3.9/1.8A or less  | 
    ||
| 
         Efficiency (100/200 VAC)  | 
        
         82, 85% typ. (at 100% load)  | 
    |||||||
| 
         Leakage current (100/200 VAC)  | 
        
         0.4, 0.75 mA or less (at 100% load)  | 
    |||||||
| 
         Rush current (100/200 VAC)  | 
        
         25, 50 A or less (at 100% load with a +25°C 77°F cold start)  | 
        
         18/36A or less  | 
    ||||||
| 
         Output characteristics  | 
        
         Rated voltage  | 
        
         24V  | 
    ||||||
| 
         Variable voltage range  | 
        
         ±5% (with V.ADJ)  | 
    |||||||
| 
         Rated current  | 
        
         2.1A (Class2)  | 
        
         3.2A  | 
        
         4.5A  | 
        
         6.5A  | 
        
         12.5A  | 
    |||
| 
         Ripple/noise voltage  | 
        
         180mV (p-p) or less  | 
    |||||||
| 
         Input fluctuation  | 
        
         0.4% or less  | 
    |||||||
| 
         Load fluctuation  | 
        
         1.5% or less  | 
    |||||||
| 
         Temperature fluctuation  | 
        
         0.02%/°C or less  | 
    |||||||
| 
         Startup time  | 
        
         500 ms or less (when the ambient usage temperature is between 0 and +55°C 32 and 131°F with rated I/O conditions)  | 
    |||||||
| 
         Output holding time  | 
        
         20 ms or more (when the ambient usage temperature is +25°C 77°F and with rated I/O conditions)  | 
    |||||||
| 
         Protection  | 
        
         Overcurrent protection  | 
        
         Constant current drop method, automatic recovery, 2.7 A or more  | 
        
         Constant current drop method, automatic recovery, 4.0 A or more  | 
        
         Constant current drop method, automatic recovery, 5.3 A or more  | 
        
         Constant current drop method, automatic recovery, 7.9 A or more  | 
        
         Constant current drop method, automatic recovery, 15.6 A or more  | 
    ||
| 
         Overvoltage protection  | 
        
         Activates at 26.4 V or more, voltage interruption method, recovers when input is applied again*2  | 
    |||||||
| 
         Display  | 
        
         Display power  | 
        
         3-digit 7-segment LED (character height: 10 mm 0.39")  | 
    ||||||
| 
         Power off memory time  | 
        
         Approx. 10 years (at +20°C 68°F)  | 
    |||||||
| 
         Display resolution  | 
        
         0.1A/0.4V /1%  | 
    |||||||
| 
         Applicable standards  | 
        
         Safety standards  | 
        
         UL: UL508, UL60950-1; C-UL: CSA C22.2 number 14-M95, CSA C22.2 number 60950-1-03; EN: EN60950-1, EN50178; IEC: IEC60950-1  | 
    ||||||
| 
         EMC standard  | 
        
         FCC Part 15 B Class A, EN55011 Class A, EN61000-6-2  | 
    |||||||
| 
         Limits for harmonic current emissions  | 
        
         EN61000-3-2*3  | 
    |||||||
| 
         Other  | 
        
         Parallel operation  | 
        
         Possible (requires OP-42207)*4  | 
    ||||||
| 
         Series operation  | 
        
         Possible (requires external diode)*4  | 
    |||||||
| 
         Cooling method  | 
        
         Natural air cooling  | 
    |||||||
| 
         Environmental resistance  | 
        
         Insulation resistance  | 
        
         100 MΩ or more at 500 VDC  | 
    ||||||
| 
         Ambient temperature  | 
        
         -10 to +55 °C 14 to 131 °F (No freezing) (see the derating characteristics)  | 
    |||||||
| 
         Relative humidity  | 
        
         25 to 85 % RH (No condensation)  | 
    |||||||
| 
         Storage temperature  | 
        
         -20 to +70 °C -4 to 158 °F (No freezing)  | 
    |||||||
| 
         Withstand voltage  | 
        
         3.0 kVAC, 50/60 Hz, 1 min (across input and output terminals)  | 
    |||||||
| 
         Vibration resistance  | 
        
         10 to 57 Hz, Double amplitude 0.3 mm 0.01", 57 to 500 Hz, 19.6 m/s2 (2 G), cycle: 5.5 minutes, 2 hours in each of the X, Y, and Z directions  | 
    |||||||
| 
         Shock resistance  | 
        
         Peak acceleration: 300 m/s2, 2 times in each of the X, Y, and Z directions  | 
    |||||||
| 
         Weight  | 
        
         Approx. 270 g  | 
        
         Approx. 470 g  | 
        
         Approx. 490 g  | 
        
         Approx. 700 g  | 
        
         Approx. 1,540 g  | 
    |||
| 
         *1 The rated input voltage and rated frequency when applying for safety standards are 100 to 240 VAC, 50/60 Hz.  | 
    ||||||||