Programmable Logic Controller

KV-8000 series

Catalogs View Catalog

Temperature input unit,input: 4 KV-NC4TP

KV-NC4TP - Temperature input unit,input: 4

*Please note that accessories depicted in the image are for illustrative purposes only and may not be included with the product.

Software

  • CE Marking
  • UL Listing(c/us)

Specifications

Model

KV-NC4TP

Temperature input unit

Number of inputs

4 *1

Input

Thermocouple, Platinum resistance thermometer

Input range

Thermocouple

K: -270.0 to 1372.0°C -454 to 2501.6°F
J: -210.0 to 1200.0°C -346 to 2192°F
T: -270.0 to 400.0°C -454 to 752°F
E: -270.0 to 1000.0°C -454 to 1832°F
N: -270.0 to 1300.0°C -454 to 2372°F
R: -50.0 to 1768.0°C -58 to 3214.4°F
S: -50.0 to 1768.0°C -58 to 3214.4°F
B: 0.0 to 1820.0°C 32 to 3308°F
WRe5-26: 0.0 to 2315.0°C 32 to 4199°F

Platinum resistance thermometer

Pt100: -200.0 to 850.0°C -328 to 1562°F
JPt100: -200.0 to 600.0°C -328 to 1112°F

Overall accuracy

Thermocouple

±(0.2% of F.S. +1°C 1.8°F) (at 25°C ±5°C 77°F ±9°F)
±(0.4% of F.S. +1°C 1.8°F) (at 0 to 55°C 32 to 131°F)

Platinum resistance thermometer

±0.2% of F.S. (at 25°C ±5°C 77°F ±9°F)
±0.4% of F.S. (at 0 to 55°C 32 to 131°F)

Allowable wiring resistance

100 Ω max./wire
(no variation allowed among three wires)

Conversion speed

125 ms/channel

Isolation method

Between input terminals and base unit:
Photocoupler/semiconductor relay/transformer isolation
Between channels: (When resistance thermometer is not used):
Semiconductor relay isolation;
(When resistance thermometer is used): No isolation

Special function

Channel skip, disconnection detection,
averaging (time average, count average, moving average),
special data offset, peak-/bottom-hold, alarm,
abnormal input setting

Internal current consumption

40 mA or less

Weight

Approx. 110 g

*1 Individual setting is possible for each channel.

Data Sheet (PDF) Other Models