Programmable Logic Controller

KV-8000 series

Catalogs View Catalog

Database Communication Unit KV-XCM02

KV-XCM02 - Database Communication Unit

*Please note that accessories depicted in the image are for illustrative purposes only and may not be included with the product.

Software

  • CE Marking
  • UL Listing(c/us)

Specifications

Model

KV-XCM02

General specifications

Power voltage

System configuration using a KV-5000/3000 Series expansion unit: 24 VDC (±10%)
System configuration using only a KV‑8000/7000 Series expansion unit: 24 VDC (−15%/+20%)
*1

Operating ambient temperature

System configuration using a KV-5000/3000 Series expansion unit: 0 to +50°C 32 to 122°F (No freezing)
System configuration using only a KV‑8000/7000 Series expansion unit: 0 to +55°C 32 to 131°F (No freezing)
*2*3

Operating ambient humidity

System configuration using a KV-5000/3000 Series expansion unit: 10 to 95% RH (No condensation)
System configuration using only a KV‑8000/7000 Series expansion unit: 5 to 95% RH (No condensation)
*2

Storage ambient temperature

System configuration using a KV-5000/3000 Series expansion unit: −20 to +70°C -4 to +158°F
System configuration using only a KV‑8000/7000 Series expansion unit: −25 to +75°C -13 to +167°F
*2

Storage relative humidity

System configuration using a KV-5000/3000 Series expansion unit: 10 to 95% RH (No condensation)
System configuration using only a KV‑8000/7000 Series expansion unit: 5 to 95% RH (No condensation)
*2

Operating environment

No dust or corrosive gas

Operating altitude

2000 m 6561.7' or less

Noise immunity

1500 Vp-p or more; Pulse duration: 1 μs, 50 ns (based on noise simulator); IEC standard-compliant (IEC 61000-4-2/3/4/6)

Withstand voltage

1500 VAC for one minute (between the power terminals and the I/O terminals, and between the external terminals and the case)

Insulation resistance

50 MΩ or more (between the power terminals and the I/O terminals and between the external terminals and the case, with 500 VDC megohmmeter)

Vibration resistance

Intermittent vibration

Frequency 5 to 9 Hz

Half amplitude 3.5 mm 0.14"*4

Frequency 9 to 150 Hz

Acceleration 9.8 m/s2 32.2'/s2*4

Continuous vibration

Frequency 5 to 9 Hz

Half amplitude 1.75 mm 0.07"*4

Frequency 9 to 150 Hz

Acceleration 4.9 m/s2 16.1'/s2*4

Shock resistance

Acceleration: 150 m/s2 492.1'/s2, Application time: 11 ms, 2 times in each of the X, Y, and Z directions

Pollution degree

2

Common specifications

Connectable CPU unit

KV-8000A/7500/7300

Max. number of connectable units

14

Connection interface

RJ-45 8-position modular connector × 2 ports

Transmission rate

10BASE-T: 10 Mbps
100BASE-TX: 100 Mbps
1000BASE-T: 1000 Mbps
*5

Transmission media

10BASE-T: Category 3 or higher UTP or STP (STP is recommended)
100BASE-TX: Category 5 or higher UTP or STP (STP is recommended)
1000BASE-T: Category 5e or higher UTP or STP (double-shielded STP is recommended)
*6

Maximum cable length

100 m 328.1'*7

Maximum number of connectable hubs

10BASE-T: 4
100BASE-TX: 2
1000BASE-T: 1
*8

Ethernet functions

Socket communication, FTP server, FTP client, upper link communication, etc.

Internal current consumption

200 mA or less

Weight

Approx. 190 g 6.71 oz

Compatibility specifications

Supported databases

Microsoft SQL Server, PostgreSQL, MariaDB, MySQL, Oracle Database*9

Maximum number of connections

4

Supported SQL

INSERT*10, UPDATE, SELECT*10, DELETE, TRUNCATE, Stored procedure/Stored function execution

Maximum number of supported columns

1024 (Microsoft SQL Server); 1000 (PostgreSQL, MariaDB, MySQL, Oracle Database)

Maximum record storage size

200000 bytes*11

Buffer retransmission function

Function that buffers SQL statements if communication fails to enable retransmission when communication is restored Maximum buffer capacity: 1 GB per connection (SD card required)

*1 Supplied via the CPU unit or expansion unit.
*2 Guaranteed range in which the system can be used.
*3 Specified according to the temperature in the control panel on the lower side of the unit.
*4 Compliant with JIS B 3502 and IEC 61131-2, 10 times in each of the X, Y, and Z directions (for 100 min.)
*5 10 Mbps/100 Mbps/1000 Mbps MDI/MDI-X automatic switching function supported.
*6 STP = Shielded twisted pair cable; UTP = Unshielded twisted pair cable
*7 The maximum cable length refers to the distance between the KV-XCM02 and the Ethernet switch.
*8 The maximum number is not limited when an Ethernet switch is used.
*9 Refer to the manual for supported database versions.
*10 Multi-extraction/insertion supported.
*11 This is the maximum size of the data saving area reserved for CPU unit devices.