Clamp-On Flow Sensor
FD-H series
Specs Clamp-On Flow Sensor FD-H series
Flow Sensors
| 
         Model  | 
        
         FD-H10  | 
        
         FD-H10K  | 
        
         FD-H20  | 
        
         FD-H20K  | 
        
         FD-H32  | 
        
         FD-H32K  | 
    |||
| 
         Image  | 
        
         
  | 
        
         
  | 
        
         
  | 
        
         
  | 
        
         
  | 
        
         
  | 
    |||
| 
         Type  | 
        
         Standard model  | 
        
         High-temperature model  | 
        
         Standard model  | 
        
         High-temperature model  | 
        
         Standard model  | 
        
         High-temperature model  | 
    |||
| 
         Supported pipe diameter  | 
        
         1/4" (8A), ø13–16 ø0.51"-0.63"  | 
        
         1/2" (15A), ø18–23 ø0.71"-0.91"  | 
        
         1" (25A), ø28–37 ø1.10"-1.46"  | 
    ||||||
| 
         Supported pipe materials  | 
        
         Metal piping, hard plastic piping*1  | 
    ||||||||
| 
         Supported fluids  | 
        
         All fluids (water, oil, chemicals, etc.)*1  | 
    ||||||||
| 
         Supported fluid temperature  | 
        
         0–85°C 32–185°F (no freezing on pipe surface)*2  | 
        
         0–180°C 32–356°F (no freezing on pipe surface)*2*10  | 
        
         0–85°C 32–185°F (no freezing on pipe surface)*2  | 
        
         0–180°C 32–356°F (no freezing on pipe surface)*2*10  | 
        
         0–85°C 32–185°F (no freezing on pipe surface)*2  | 
        
         0–180°C 32–356°F (no freezing on pipe surface)*2*10  | 
    |||
| 
         Maximum rated flow  | 
        
         1/4" (8A) : 20 L/min  | 
        
         1/2" (15A) : 60 L/min 15.9 gal/min  | 
        
         1" (25A) : 200 L/min 52.8 gal/min  | 
    ||||||
| 
         Zero cut flow rate  | 
        
         0.3 L/min 0.08 gal/min (variable, initial value)  | 
        
         0.5 L/min 0.13 gal/min (variable, initial value)  | 
        
         1.0 L/min 0.3 gal/min (variable, initial value)  | 
    ||||||
| 
         Detection principle  | 
        
         Delta TOF + Pulse Doppler  | 
    ||||||||
| 
         Function for automatic correction for speed of sound in liquid  | 
        
         Yes  | 
    ||||||||
| 
         Display  | 
        
         QVGA 2.0 model: color LCD, status indicator light  | 
    ||||||||
| 
         Display update cycle  | 
        
         Approx. 10 times/second  | 
    ||||||||
| 
         Display resolution  | 
        
         Instantaneous flow  | 
        
         0.01/0.1/1 (L/min) (default value: 0.1)  | 
        
         0.01/0.1/1 (L/min) (default value: 1)  | 
    ||||||
| 
         Integrated flow  | 
        
         0.01/0.1/1 (L) (default value: 0.1; up to 8 digits)  | 
        
         0.01/0.1/1 (L) (default value: 1; up to 8 digits)  | 
    |||||||
| 
         Response time  | 
        
         0.5 s / 1.0 s / 2.5 s / 5.0 s / 10.0 s / 30.0 s / 60.0 s / 120.0 s / 200.0 s  | 
    ||||||||
| 
         Measurement accuracy  | 
        
         Between 10 and 100% of F.S.: ±3.0% of RD*3*4  | 
    ||||||||
| 
         Repeatability  | 
        
         0.5 s: ±1.0%, 1 s: ±0.7%, 2.5 s: ±0.45%, 5 s: ±0.3%, 10 s: ±0.2%, 30 s: ±0.15%, 60 s: ±0.1% of F.S.*3*5  | 
    ||||||||
| 
         Hysteresis  | 
        
         Variable  | 
    ||||||||
| 
         Flow units  | 
        
         L/min m3/h G/min  | 
    ||||||||
| 
         Pulse output increments (L)  | 
        
         0.02–999.99  | 
    ||||||||
| 
         Pipe temperature measurement accuracy  | 
        
         ±2.0°C ±3.5°F (pipe temperature 0–50°C 32–122°F) , ±3.0°C ±5.4°F (pipe temperature 50–85°C 122–185°F) (ambient temperature of 25°C 77°F)*3  | 
        
         —  | 
        
         ±2.0°C ±3.5°F (pipe temperature 0–50°C 32–122°F) , ±3.0°C ±5.4°F (pipe temperature 50–85°C 122–185°F) (ambient temperature of 25°C 77°F)*3  | 
        
         —  | 
        
         ±2.0°C ±3.5°F (pipe temperature 0–50°C 32–122°F) , ±3.0°C ±5.4°F (pipe temperature 50–85°C 122–185°F) (ambient temperature of 25°C 77°F)*3  | 
        
         —  | 
    |||
| 
         Network support  | 
        
         IO-Link*6  | 
    ||||||||
| 
         Heat calculation function  | 
        
         Unit  | 
        
         MJ/h kW kBTU/h*7  | 
    |||||||
| 
         Display resolution  | 
        
         Instantaneous value (MJ/h): 0.01/0.1/1 (default value 0.1); Integrated value (MJ): 0.01/0.1/1 (default value 0.1)*7  | 
    ||||||||
| 
         Pulse output increments (MJ)  | 
        
         0.02–999.99*7  | 
    ||||||||
| 
         Data accumulation  | 
        
         Accumulation period  | 
        
         Approx. 1 year  | 
    |||||||
| 
         Data reading  | 
        
         USB2.0  | 
    ||||||||
| 
         Power I/O connector  | 
        
         M12 8-pin connector (male)  | 
    ||||||||
| 
         I/O (switchable)  | 
        
         Output (Ch1/2/3/4)  | 
        
         Instantaneous flow mode / area mode / pulse output mode / integrated flow mode / bubble detection mode / error output  | 
    |||||||
| 
         Analog output (Ch1/2)  | 
        
         4–20 mA/0–20 mA (switchable), load resistance 500 Ω or less  | 
    ||||||||
| 
         External input (Ch2/3)  | 
        
         Integrated reset input / flow-rate zero input / zero-point adjustment input / bank input  | 
    ||||||||
| 
         Power supply  | 
        
         Power voltage  | 
        
         20–30 VDC, ripple (P-P) 10% included, Class 2/LPS  | 
    |||||||
| 
         Current consumption  | 
        
         240 mA or less (when using flow sensor standalone; with analog output; excluding load current)*8  | 
    ||||||||
| 
         Protection circuit  | 
        
         Protection against reverse power connection, power supply surges, output short circuits, and output surges  | 
    ||||||||
| 
         Environmental resistance  | 
        
         Enclosure rating  | 
        
         IP65/67 (IEC 60529)*9  | 
    |||||||
| 
         Ambient temperature  | 
        
         Sensor head: −20 to +60°C –4 to +140°F (no freezing); Display unit: −20 to +50°C –4 to +122°F (no freezing)*2  | 
    ||||||||
| 
         Relative humidity  | 
        
         35–85% RH (no condensation)  | 
    ||||||||
| 
         Vibration resistance  | 
        
         10–500 Hz; Power spectral density: 0.816 G2/Hz; X, Y and Z directions  | 
    ||||||||
| 
         Shock resistance  | 
        
         100 m/s2 (approx. 10 G), 16 ms pulses, 1000 times each for X, Y and Z axes  | 
    ||||||||
| 
         Material  | 
        
         Display unit  | 
        
         Body: PPS/PET/POM; Display window: PAR  | 
    |||||||
| 
         Sensor head  | 
        
         Body: PPS/PET/PAR/SUS304  | 
        
         Body: PEEK/PPS/PET/PAR/SUS304  | 
        
         Body: PPS/PET/PAR/SUS304  | 
        
         Body: PEEK/PPS/PET/PAR/SUS304  | 
        
         Body: PPS/PET/PAR/SUS304  | 
        
         Body: PEEK/PPS/PET/PAR/SUS304  | 
    |||
| 
         Weight  | 
        
         approx. 440 g 15.52 oz  | 
        
         approx. 490 g 17.28 oz  | 
        
         approx. 480 g 16.93 oz  | 
        
         approx. 540 g 19.05 oz  | 
        
         approx. 620 g 21.87 oz  | 
        
         approx. 680 g 23.99 oz  | 
    |||
| 
         *1 For fluids through which ultrasonic waves propagate, and which do not contain a large quantity of bubbles. Detection may be unstable depending on the type and condition of the pipe.  | 
    |||||||||
Flow Sensors
| 
         Model  | 
        
         FD-H22F  | 
        
         FD-H32F  | 
        
         FD-H47F  | 
        
         FD-H63F  | 
    |||
| 
         Image  | 
        
         
  | 
        
         
  | 
        
         
  | 
        
         
  | 
    |||
| 
         Type  | 
        
         Hose model  | 
    ||||||
| 
         Supported pipe diameter  | 
        
         ø13–22.9 ø0.51"-0.90"  | 
        
         ø23–32.9 ø0.91"-1.295"  | 
        
         ø33–47.9 ø1.299"-1.886"  | 
        
         ø48–63 ø1.89"-2.48"  | 
    |||
| 
         Supported pipe materials  | 
        
         Soft plastic piping, all hoses (braided hoses, pressure-resistant rubber hoses, etc.)*1  | 
    ||||||
| 
         Supported fluids  | 
        
         All fluids (water, oil, chemicals, etc.)*1  | 
    ||||||
| 
         Supported fluid temperature  | 
        
         0–100°C 32–212°F (no freezing on pipe surface)*2  | 
    ||||||
| 
         Maximum rated flow  | 
        
         60 L/min  | 
        
         200 L/min  | 
        
         300 L/min  | 
        
         500 L/min  | 
    |||
| 
         Zero cut flow rate  | 
        
         0.5 L/min  | 
        
         1.0 L/min  | 
        
         2.0 L/min  | 
        
         5.0 L/min  | 
    |||
| 
         Detection principle  | 
        
         Delta TOF  | 
    ||||||
| 
         Function for automatic correction for speed of sound in liquid  | 
        
         —  | 
    ||||||
| 
         Display  | 
        
         QVGA 2.0 model: color LCD, status indicator light  | 
    ||||||
| 
         Display update cycle  | 
        
         Approx. 10 times/second  | 
    ||||||
| 
         Display resolution  | 
        
         Instantaneous flow  | 
        
         0.01/0.1/1 (L/min) (default value: 0.1)  | 
        
         0.01/0.1/1 (L/min) (default value: 1)  | 
    ||||
| 
         Integrated flow  | 
        
         0.01/0.1/1 (L) (default value: 0.1; up to 8 digits)  | 
        
         0.01/0.1/1 (L) (default value: 1; up to 8 digits)  | 
    |||||
| 
         Response time  | 
        
         0.5 s / 1.0 s / 2.5 s / 5.0 s / 10.0 s / 30.0 s / 60.0 s / 120.0 s / 200.0 s  | 
    ||||||
| 
         Measurement accuracy  | 
        
         —  | 
    ||||||
| 
         Repeatability  | 
        
         0.5 s: ±1.0%, 1 s: ±0.7%, 2.5 s: ±0.45%, 5 s: ±0.3%, 10 s: ±0.2%, 30 s: ±0.15%, 60 s: ±0.1% of F.S.*3*4  | 
    ||||||
| 
         Hysteresis  | 
        
         Variable  | 
    ||||||
| 
         Flow units  | 
        
         L/min m3/h G/min  | 
    ||||||
| 
         Pulse output increments (L)  | 
        
         0.02–999.99  | 
    ||||||
| 
         Pipe temperature measurement accuracy  | 
        
         —  | 
    ||||||
| 
         Network support  | 
        
         IO-Link*5  | 
    ||||||
| 
         Heat calculation function  | 
        
         Unit  | 
        
         MJ/h kW kBTU/h*6  | 
    |||||
| 
         Display resolution  | 
        
         Instantaneous value (MJ/h): 0.01/0.1/1 (default value 0.1); Integrated value (MJ): 0.01/0.1/1 (default value 0.1)*6  | 
    ||||||
| 
         Pulse output increments (MJ)  | 
        
         0.02–999.99*6  | 
    ||||||
| 
         Data accumulation  | 
        
         Accumulation period  | 
        
         Approx. 1 year  | 
    |||||
| 
         Data reading  | 
        
         USB2.0  | 
    ||||||
| 
         Power I/O connector  | 
        
         M12 8-pin connector (male)  | 
    ||||||
| 
         I/O (switchable)  | 
        
         Output (Ch1/2/3/4)  | 
        
         Instantaneous flow mode / area mode / pulse output mode / integrated flow mode / bubble detection mode / error output  | 
    |||||
| 
         Analog output (Ch1/2)  | 
        
         4–20 mA/0–20 mA (switchable), load resistance 500 Ω or less  | 
    ||||||
| 
         External input (Ch2/3)  | 
        
         Integrated reset input / flow-rate zero input / zero-point adjustment input / bank input  | 
    ||||||
| 
         Power supply  | 
        
         Power voltage  | 
        
         20–30 VDC, ripple (P-P) 10% included, Class 2/LPS  | 
    |||||
| 
         Current consumption  | 
        
         240 mA or less (when using flow sensor standalone; with analog output; excluding load current)*7  | 
    ||||||
| 
         Protection circuit  | 
        
         Protection against reverse power connection, power supply surges, output short circuits, and output surges  | 
    ||||||
| 
         Environmental resistance  | 
        
         Enclosure rating  | 
        
         IP65/67 (IEC 60529)*8  | 
    |||||
| 
         Ambient temperature  | 
        
         Sensor head: −20 to +60°C –4 to +140°F (no freezing); Display unit: −20 to +50°C –4 to +122°F (no freezing)*2  | 
    ||||||
| 
         Relative humidity  | 
        
         35–85% RH (no condensation)  | 
    ||||||
| 
         Vibration resistance  | 
        
         10–500 Hz; Power spectral density: 0.816 G2/Hz; X, Y and Z directions  | 
    ||||||
| 
         Shock resistance  | 
        
         100 m/s2 (approx. 10 G), 16 ms pulses, 1000 times each for X, Y and Z axes  | 
    ||||||
| 
         Material  | 
        
         Display unit  | 
        
         Body: PPS/PET/POM; Display window: PAR  | 
    |||||
| 
         Sensor head  | 
        
         Body: PPS/PET/PAR/SUS304; Cable: PVC  | 
    ||||||
| 
         Weight  | 
        
         approx. 770 g 27.16 oz  | 
        
         approx. 880 g 31.04 oz  | 
        
         approx. 1130 g 39.86 oz  | 
        
         approx. 1360 g 47.97 oz  | 
    |||
| 
         *1 For fluids through which ultrasonic waves propagate, and which do not contain a large quantity of bubbles. Detection may be unstable depending on the type and condition of the pipe.  | 
    |||||||
Temperature Sensors
| 
         Model  | 
        
         FI-T8  | 
        
         FI-T15  | 
        
         FI-T25  | 
        
         FI-T50  | 
        
         FI-T100  | 
        
         FI-T200  | 
    |||
| 
         Image  | 
        
         
  | 
        
         
  | 
        
         
  | 
        
         
  | 
        
         
  | 
        
         
  | 
    |||
| 
         Supported pipe diameter  | 
        
         1/8", 1/4"  | 
        
         3/8", 1/2"  | 
        
         3/4", 1"  | 
        
         1 1/4", 1 1/2", 2"  | 
        
         2 1/2", 3", 3 1/2", 4"  | 
        
         5", 6", 8"  | 
    |||
| 
         Supported pipe materials  | 
        
         Metal piping  | 
    ||||||||
| 
         Supported temperature range  | 
        
         −20 to +180°C –4 to +356°F*1  | 
    ||||||||
| 
         Display method  | 
        
         Organic EL, status indicator light  | 
    ||||||||
| 
         Display resolution  | 
        
         0.1°C 32.18°F  | 
    ||||||||
| 
         Response time  | 
        
         5 s (50% response), 15 s (90% response)*2  | 
    ||||||||
| 
         Display amplifier averaging time  | 
        
         0.1 s / 10.0 s / 20.0 s / 30.0 s / 60.0 s / 120.0 s / 300.0 s  | 
    ||||||||
| 
         Measurement accuracy  | 
        
         ±0.5°C ±0.9°F (pipe temperature −20 to +80°C –4 to 176°F) (ambient temperature of 25°C 77°F)*2*3  | 
    ||||||||
| 
         Hysteresis  | 
        
         Variable  | 
    ||||||||
| 
         Measurement principle  | 
        
         Pt100 4-wire type  | 
    ||||||||
| 
         Power I/O connector  | 
        
         M8 4-pin connector  | 
    ||||||||
| 
         Power supply  | 
        
         Current consumption  | 
        
         20 mA or less (excluding load current)*4  | 
    |||||||
| 
         When used standalone  | 
        
         I/O (switchable)  | 
        
         Output (Ch1/Ch2)  | 
        
         Control output: switching NPN/PNP setting  | 
    ||||||
| 
         Analog output (Ch2)  | 
        
         4–20 mA / 0–20 mA (switchable), load resistance 260 Ω or less*5  | 
    ||||||||
| 
         Power voltage  | 
        
         20–30 VDC, ripple (P-P) 10% included; Class2/LPS*5  | 
    ||||||||
| 
         Protection circuit  | 
        
         Protection against reverse power connection, power supply surges, output short circuits, and output surges*5  | 
    ||||||||
| 
         Network compatibility  | 
        
         IO-Link*6*5  | 
    ||||||||
| 
         Environmental resistance  | 
        
         Enclosure rating  | 
        
         IP65/IP67 (IEC60529)  | 
    |||||||
| 
         Ambient temperature  | 
        
         –10 to +60°C -14 to +140°F (no freezing)  | 
    ||||||||
| 
         Relative humidity  | 
        
         35–85% RH (no condensation)  | 
    ||||||||
| 
         Vibration resistance  | 
        
         10–500 Hz; power spectral density: 0.816 G2/Hz; X, Y and Z directions  | 
    ||||||||
| 
         Shock resistance  | 
        
         100 m/s2 (approx. 10 G), 16 ms pulses, 1000 times each for X, Y and Z directions  | 
    ||||||||
| 
         Material  | 
        
         Display amplifier  | 
        
         PBT / PAR / POM / SUS303  | 
    |||||||
| 
         Sensor head  | 
        
         Head: PPS / SUS303 / Sn; Pipe clamp unit: SUS304; Cable: fluororesin  | 
    ||||||||
| 
         Display amplifier mounting bracket  | 
        
         SUS304  | 
    ||||||||
| 
         Weight  | 
        
         Approx. 70 g 2.47 oz  | 
        
         Approx. 80 g 2.82 oz  | 
        
         Approx. 65 g 2.29 oz  | 
        
         Approx. 70 g 2.47 oz  | 
        
         Approx. 100 g 3.53 oz  | 
        
         Approx. 120 g 4.23 oz  | 
    |||
| 
         *1 When pipe temperature is 100°C 212°F or more, the display amplifier cannot be mounted on the pipe clamp unit. Install the amplifier so it is insulated from the heat from the pipe.  | 
    |||||||||
Concentration Sensors
| 
         Model  | 
        
         FI-C20D  | 
        
         FI-C40F  | 
    |||
| 
         Image  | 
        
         
  | 
        
         
  | 
    |||
| 
         Type  | 
        
         Probe type  | 
        
         Pipe type  | 
    |||
| 
         Attachment  | 
        
         —  | 
        
         FI-CF1/3, FI-CF2/4  | 
    |||
| 
         Detection principle  | 
        
         Refractive index (surface light source)  | 
    ||||
| 
         Rated concentration range  | 
        
         Brix: 0–20% (nD: 1.32500–1.37000)  | 
        
         Brix: 0–40% (nD: 1.32500–1.41000)  | 
    |||
| 
         Display method  | 
        
         Status indicator light  | 
    ||||
| 
         Display range  | 
        
         Brix: 0–25%  | 
        
         Brix: 0–50%  | 
    |||
| 
         Supported fluids  | 
        
         Non-corrosive aqueous solutions (such as water-soluble coolants, mold release agents, etc.)*1  | 
    ||||
| 
         Supported fluid temperature  | 
        
         0–70°C 32–158°F (no freezing)  | 
    ||||
| 
         Connection diameter  | 
        
         —  | 
        
         FI-CF1: Rc3/4 (20 A); FI-CF3: NPT3/4  | 
    |||
| 
         Rated pressure range  | 
        
         1.0 MPa or less  | 
    ||||
| 
         Pressure resistance  | 
        
         2.0 MPa  | 
    ||||
| 
         Display resolution  | 
        
         Brix: 0.01/0.1% (default value: 0.1)  | 
    ||||
| 
         Response time  | 
        
         1.0 s / 2.5 s / 5.0 s / 10.0 s / 30.0 s / 60.0 s / 120.0 s / 200.0 s  | 
    ||||
| 
         Measurement accuracy  | 
        
         Brix: ±0.2%*2*3 (nD: ±0.0003)  | 
    ||||
| 
         Concentration unit  | 
        
         Brix nD*4  | 
    ||||
| 
         Temperature measurement accuracy  | 
        
         ±1.0°C 1.8°F*2  | 
    ||||
| 
         Power supply  | 
        
         Current consumption  | 
        
         25 mA or less  | 
    |||
| 
         Environmental resistance  | 
        
         Enclosure rating  | 
        
         IP65/IP67 (IEC60529)  | 
    |||
| 
         Ambient temperature  | 
        
         –10 to +60°C 14 to +140°F (no freezing)  | 
    ||||
| 
         Relative humidity  | 
        
         35–85% RH (no condensation)  | 
    ||||
| 
         Vibration resistance  | 
        
         10–500 Hz; Power spectral density: 0.816 G2/Hz; X, Y and Z directions  | 
    ||||
| 
         Shock resistance  | 
        
         100 m/s2 (approx. 10 G), 16 ms pulses, 1000 times each for X, Y and Z directions  | 
    ||||
| 
         Material  | 
        
         Liquid end materials  | 
        
         Sensor element: synthetic quartz  | 
        
         Sensor element: sapphire  | 
    ||
| 
         Other materials  | 
        
         Indicator light: PPSU / TPU / PBT  | 
        
         Body: SUS304; PPS indicator light: PPSU / TPU / PBT  | 
    |||
| 
         Weight  | 
        
         Approx. 480 g 16.93 oz  | 
        
         Approx. 410 g 14.46 oz  | 
    |||
| 
         *1 Use water as the solvent, and use materials that are soluble in water. If the particles are not water soluble, such as with slurry, the refractive index may not change.  | 
    |||||
Standalone Display Unit
| 
         Model  | 
        
         FI-1000  | 
    |||
| 
         Image  | 
        
         
  | 
    |||
| 
         Display  | 
        
         QVGA 2.0 model: color LCD, status indicator light  | 
    |||
| 
         Display update cycle  | 
        
         Approx. 10 times/second  | 
    |||
| 
         Network support  | 
        
         IO-Link*1  | 
    |||
| 
         Heat calculation function  | 
        
         Unit  | 
        
         MJ/h, kW, kBTU/h, GJ/h, MW, MBTU/h*2  | 
    ||
| 
         Display resolution  | 
        
         Instantaneous value (MJ/h): 0.01/0.1/1 (default value 0.1); Integrated value (MJ): 0.01/0.1/1 (default value 0.1)*2  | 
    |||
| 
         Pulse output increments (MJ)  | 
        
         0.02–999.99*2  | 
    |||
| 
         Data accumulation  | 
        
         Accumulation period  | 
        
         Approx. 1 year  | 
    ||
| 
         Data reading  | 
        
         USB2.0  | 
    |||
| 
         Power I/O connector  | 
        
         M12 8-pin connector (male)  | 
    |||
| 
         I/O (switchable)  | 
        
         Output (Ch1/2/3/4)  | 
        
         NPN/PNP setting switching, open collector output 30 VDC or less, max. 100 mA/ch or less, residual voltage 2.5 V or less  | 
    ||
| 
         Analog output (Ch1/2)  | 
        
         4–20 mA/0–20 mA (switchable), load resistance 500 Ω or less  | 
    |||
| 
         External input (Ch2/3)  | 
        
         Short circuit current: 1.5 mA or less; input time: 20 ms or more  | 
    |||
| 
         Power supply  | 
        
         Power voltage  | 
        
         20–30 VDC, ripple (P-P) 10% included, Class 2/LPS  | 
    ||
| 
         Current consumption  | 
        
         55 mA or less (display unit standalone, excluding load current)*3  | 
    |||
| 
         Protection circuit  | 
        
         Protection against reverse power connection, power supply surges, output short circuits, and output surges  | 
    |||
| 
         Environmental resistance  | 
        
         Enclosure rating  | 
        
         IP65/IP67 (IEC60529)*4  | 
    ||
| 
         Ambient temperature  | 
        
         –20°C to +50°C –4°F to +122°F (no freezing)  | 
    |||
| 
         Relative humidity  | 
        
         35–85% RH (no condensation)  | 
    |||
| 
         Vibration resistance  | 
        
         10–500 Hz; Power spectral density: 0.816 G2/Hz; X, Y and Z directions  | 
    |||
| 
         Shock resistance  | 
        
         100 m/s2 (approx. 10 G), 16 ms pulses, 1000 times each for X, Y and Z directions  | 
    |||
| 
         Material  | 
        
         Body: PPS / PET / POM; Display window: PAR  | 
    |||
| 
         Weight  | 
        
         Approx. 120 g 4.23 oz  | 
    |||
| 
         *1 Supports IO-Link specification v.1.1/COM2 (38.4 kbps). Setting files can be downloaded from the KEYENCE website (www.keyence.com). IO-Link is a trademark or registered trademark of PROFIBUS Nutzerorganisation e.V. (PNO).  | 
    ||||