Data utilization unit KV-XD02

KV-XD02 - Data utilization unit

*Please note that accessories depicted in the image are for illustrative purposes only and may not be included with the product.

Data Sheet (PDF)

Manuals

CAD Data

360°view (3D PDF)

Software

  • CE Marking
  • UL Listing(c/us)

Specifications

Model

KV-XD02

Unit specifications

Operating ambient temperature

System configuration using a KV-5000/3000 Series expansion unit: 0 to +50°C 32 to 122°F (No freezing)*1*2
System configuration using only a KV-8000/7000 Series expansion unit: 0 to +55°C 32 to 131°F (No freezing)*1*2

Operating ambient humidity

System configuration using a KV-5000/3000 Series expansion unit: 10 to 95% RH (No condensation)*1
System configuration using only a KV-8000/7000 Series expansion unit: 5 to 95% RH (No condensation)*1

Storage ambient temperature

System configuration using a KV-5000/3000 Series expansion unit: −20 to +70°C -4 to +158°F*1
System configuration using only a KV-8000/7000 Series expansion unit: −25 to +75°C -13 to +167°F*1

Storage relative humidity

System configuration using a KV-5000/3000 Series expansion unit: 10 to 95% RH (No condensation)*1
System configuration using only a KV-8000/7000 Series expansion unit: 5 to 95% RH (No condensation)*1

Power voltage

When using a power supply terminal block

System configuration using a KV-5000/3000 Series expansion unit: 24 VDC (−10%/+10%)
System configuration using only a KV-8000/7000 Series expansion unit: 24 VDC (−15%/+20%)

When using the KV-PU1

System configuration using a KV-5000/3000 Series expansion unit: 100 to 240 VAC (−15%/+10%)
System configuration using only a KV-8000/7000 Series expansion unit: 100 to 240 VAC (−15%/+10%)

Common specifications

Connectable CPU unit

KV-8000 Series

Max. number of connectable units

1

Connection interface

RJ-45 8-position modular connector × 2 ports

Transmission rate

100 Mbps, 1000 Mbps *3

Transmission media

100 Mbps: Category 5 or higher UTP or STP (STP is recommended)
1000 Mbps: Category 5e or higher UTP or STP (double-shielded STP is recommended)
*4

Maximum cable length

100 Mbps: 100 m 328.1'
1000 Mbps: 100 m 328.1'
*5

Maximum number of connectable hubs

100 Mbps: 2
1000 Mbps: 1
*6

Internal current consumption

500 mA or less

Weight

Approx. 320 g 11.30 oz

Other general specifications

Same as CPU unit

*1 Guaranteed range in which the system can be used.
*2 Specified according to the temperature in the control panel on the lower side of the unit.
*3 100 Mbps/1000 Mbps MDI/MDI-X automatic switching function supported.
*4 STP = Shielded twisted pair cable; UTP = Unshielded twisted pair cable.
*5 The maximum cable length refers to the distance between the KV-XD02 and the Ethernet switch.
*6 The maximum number is not limited when an Ethernet switch is used.

Data Sheet (PDF) Other Models