SPECIFICATIONS

Select Language

Model

KV-NC8ER

Expansion output unit

External connectionmethod

Relay

External connection method

European terminal block

Rated load

250 VAC/30 VDC, 2 A

Leakage current (when output is OFF)

Residual voltage (at ON)

ON resistance

50mΩ or less

Minimum applicable load

100 µA/100 mVDC
(Reference value)

Common method

4 points/1 common
(4 terminals)*1

Response time

OFF to ON

10ms or less

ON to OFF

Relay life

Electrical : 100000 cycles or more (20 cycles/minute) Mechanical : 20000000 cycles or more

Relay replacement

Not possible

Internal current consumption

70mA or less

Weight

Approx. 130 g

*1 The KV-NC8ER has four C0s and four C1s, and each set of C0s and C1s is shorted internally.
(The sets of C0s and C1s are independent.)