Programmable Logic Controller

KV-8000 series

Catalogs View Catalog

A/D Conversion unit,4-point type KV-NC4AD

KV-NC4AD - A/D Conversion unit,4-point type

*Please note that accessories depicted in the image are for illustrative purposes only and may not be included with the product.

Data Sheet (PDF)

Manuals

CAD Data

360°view (3D PDF)

Software

  • CE Marking
  • UL Listing(c/us)

Specifications

Model

KV-NC4AD

Conversion speed

80 μs/channel*1

Conversion

A/D conversion

Points

4 (single end)

Range/resolution

Voltage

-10 V to +10 V

1/8000 2.5 mV

0 to 10 V

1/4000 2.5 mV

0 to 5 V

1/4000 1.25 mV

1 to 5 V

1/3200 1.25 mV

Current

0 to 20 mA

1/4000 5 μA

4 to 20 mA

1/3200 5 μA

Conversion precision

Voltage

Without temperature
compensation

±0.3% of F.S. (at 25°C ±5°C 77°F ±9°F)
±0.5% of F.S. (at 0 to 55°C 32 to 131°F)

With temperature
compensation

±0.3% of F.S. (at 0 to 55°C 32 to 131°F)

Current

Without temperature
compensation

±0.4% of F.S. (at 25°C ±5°C 77°F ±9°F)
±0.6% of F.S. (at 0 to 55°C 32 to 131°F)

With temperature
compensation

±0.4% of F.S. (at 0 to 55°C 32 to 131°F)

Input resistance

Voltage

5 MΩ

Current

250 Ω

Absolute maximum input

Voltage

±15 V

Current

±30 mA

Isolation method

Between analog input

Isolated (photocoupler, transformer)

Between analogu input channels

No isolation

Minimum load resistance

Voltage

Maximum load resistance

Current

Special functions

Input range switching,
temperature fluctuation compensation enabling/disabling,
channel skip, scaling, special data offset, peak-/bottom-hold,
zero clip, zero shift, comparator,
averaging (time-specified, count-specified, moving average),
disconnection detection,

*1 When the temperature fluctuation compensation is used, the temperature fluctuation compensation time of 80 μs will be added regardless of the number of channels being used.

Data Sheet (PDF) Other Models